Description for Schneider switch disconnector, Compact INS63 , 63 A, standard version with black rotary handle, 4 poles 28903
This Compact INS63 is a 4 poles non-automatic switch-disconnector with black rotary handle. It is suitable for isolation with positive contact indication, as defined by IEC 60947-1 and IEC60947-3 standards. The operational current is 63A at 415VAC in categories AC22A and AC23A. The rated voltage is 500VAC 50/60Hz or 250VDC. The black rotary handle is designed to offer easy operation and high performance in interruption of currents. Compact INS63 is a class II insulation level front-face device as per IEC 60664 standard.
            Specifications
| Range | ComPact | 
|---|---|
| Product name | ComPacT INS | 
| Product or component type | Switch disconnector | 
| Poles description | 4P | 
| Network type | DC AC  | 
| Network frequency | 50/60 Hz | 
| [Ie] rated operational current | AC-22A: 63 A AC 50/60 Hz 220/240 V AC-22A: 63 A AC 50/60 Hz 380/415 V 2 poles in series AC-22A: 63 A AC 50/60 Hz 440/480 V 4 poles in series AC-22A: 63 A AC 50/60 Hz 500 V 4 poles in series AC-23A: 40 A AC 50/60 Hz 500 V AC-23A: 63 A AC 50/60 Hz 220/240 V AC-23A: 63 A AC 50/60 Hz 380/415 V AC-23A: 63 A AC 50/60 Hz 440/480 V DC-22A: 63 A DC 50/60 Hz 125 V 2 poles in series DC-23A: 63 A DC 50/60 Hz 125 V 2 poles in series DC-22A: 63 A DC 50/60 Hz 250 V 4 poles in series DC-23A: 63 A DC 250 V 4 poles in series  | 
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz | 
| [Uimp] rated impulse withstand voltage | 8 kV | 
| [Ith] conventional free air thermal current | 63 A at 60 °C | 
| [Icm] rated short-circuit making capacity | 15 kA switch-disconnector alone 500 V AC at 50/60 Hz 75 kA with upstream protection circuit breaker 500 V AC at 50/60 Hz  | 
| [Ue] rated operational voltage | 500 V AC 50/60 Hz 250 V DC  | 
| Suitability for isolation | Yes | 
| Contact position indicator | Yes | 
| Visible break | No | 
| Pollution degree | 3 | 
| Control type | Rotary handle | 
|---|---|
| Handle colour | Black | 
| Mounting mode | Fixed | 
| Mounting support | Plate DIN rail  | 
| Upside connection | Front | 
| Downside connection | Front | 
| Cable cross section | 1.5…50 mm² | 
| Maximum power | AC-23: 15 kW at 220/240 V AC 50/60 Hz AC-23: 22 kW at 500/525 V AC 50/60 Hz AC-23: 30 kW at 380/415 V AC 50/60 Hz AC-23: 30 kW at 440 V AC 50/60 Hz  | 
| Rated duty | Uninterrupted | 
| Intermittent duty class | Class 120 - 60 % | 
| Enclosure dimensions for Ithe | 190 mm x 115 mm x 55 mm | 
| [Icw] rated short-time withstand current | 0.67 kA during 20 s conforming to IEC 60947-3 1.73 kA during 3 s conforming to IEC 60947-3 3 kA during 1 s conforming to IEC 60947-3 0.55 kA during 30 s conforming to IEC 60947-3  | 
| Mechanical durability | 20000 cycles | 
| Electrical durability | AC-22A: 1500 cycles 220/240 V AC 50/60 Hz AC-22A: 1500 cycles 380/415 V AC 50/60 Hz 4 poles in series AC-22A: 1500 cycles 440 V AC 50/60 Hz AC-22A: 1500 cycles 500 V AC 50/60 Hz AC-23A: 1500 cycles 220/240 V AC 50/60 Hz AC-23A: 1500 cycles 380/415 V AC 50/60 Hz AC-23A: 1500 cycles 440 V AC 50/60 Hz AC-23A: 1500 cycles 500 V AC 50/60 Hz DC-22A: 1500 cycles 250 V DC 50/60 Hz 4 poles in series DC-23A: 1500 cycles 250 V DC 4 poles in series  | 
| Connection pitch | 18 mm | 
| Height | 85 mm | 
| Width | 90 mm | 
| Depth | 62.5 mm | 
| Product weight | 0.6 kg | 
| standards | IEC 60947-3 IEC 60947-1  | 
|---|---|
| Product certifications | CCC KEMA-KEUR  | 
| IP degree of protection | IP40 conforming to IEC 60529 | 
| IK degree of protection | IK07 conforming to EN 50102 | 
| Ambient air temperature for operation | -25…70 °C | 
| Ambient air temperature for storage | -50…85 °C | 
| Unit Type of Package 1 | PCE | 
|---|---|
| Number of Units in Package 1 | 1 | 
| Package 1 Height | 10.000 cm | 
| Package 1 Width | 9.200 cm | 
| Package 1 Length | 10.000 cm | 
| Package 1 Weight | 650.000 g | 
| Unit Type of Package 2 | S03 | 
| Number of Units in Package 2 | 18 | 
| Package 2 Height | 30.000 cm | 
| Package 2 Width | 30.000 cm | 
| Package 2 Length | 40.000 cm | 
| Package 2 Weight | 12.064 kg | 
| Unit Type of Package 3 | P12 | 
| Number of Units in Package 3 | 144 | 
| Package 3 Height | 50.000 cm | 
| Package 3 Width | 80.000 cm | 
| Package 3 Length | 120.000 cm | 
| Package 3 Weight | 109.784 kg | 
| Warranty | 18 months | 
|---|